AUTM

Single-phase autotransformers
AUTM
AUTM
AUTM

The autotransformer is made with a single winding from which the various output voltages are taken. This type of transformer does not feature any form of galvanic separation from the primary circuit. The size-power ratio of an autotransformer is a function of the maximum (Vmax) and minimum (Vmin) input/output voltage in accordance with the following formula:

Core power handling=  (Vmax – Vmin) / Vmax X Rated output power (VA) Use the result to find the autotransformer size needed in the following table. AUTM series units for general use are manufactured on demand.

AUTM

Technical data

Power: 300 ÷ 25000 VA

Input voltage: 100 ÷ 600 VAC

Maximum current: 200A

Duty cycle: continuous
Frequency: 50/60 Hz
Protection rating: IP 00
Terminal block protection rating: IP 20
Ambient temperature: +40°C MAX
Thermal insulation class: B/130°C or F/155°C
Protection against direct and indirect contact: class I
Winding material: copper
Standards: EN61558-2-13
Approvals: cURus (insulation systems AB155 UL CSA file number E340840)

CodePower handlingLength L (mm)Depth P (mm)Height H (mm)Fixing XFixing YWeight (Kg)
AUTM10BXX10085959060702,2
AUTM20BXX200971109868874
AUTM30BXX30012010013080835,5
AUTM50BXX50013511714090888
AUTM60BXX600150110155105808,5
AUTM80BXX80015013015510510011,5
AUTM10CXX100015014015510511013
AUTM13CXX130018014518012811016
AUTM16CXX160018015518012812018
AUTM20CXX200019316019013512523
AUTM25CXX250019317019013513525
AUTM30CXX300019318019013514527
AUTM35CXX350019319019013515529
AUTM40CXX400020018029015013234
AUTM50CXX500020019029015014238
AUTM60CXX6000240170-22034020413444
AUTM70CXX7000240180-23034020414448
AUTM10CXX8000240190-24034020415455
AUTM10DXX1000028024042023515062
AUTM12DXX1200028025042023516068
AUTM15DXX1500028026042023517078
AUTM20DXX20000320330480265190115
AUTM25DXX25000330330480265200125