TTM

Three-phase/single-phase transformer isolation
TTM
TTM
TTM

Transformer series designed to distribute the load across the three power supply phases, also asymmetrically, when a single-phase output is required. Also, this model is equipped with double or reinforced insulation between the primary and secondary windings. TTM series units are designed for general use.

TTM

Technical data

Power: 100 ÷ 25000 VA
Input voltage: 400 – 415 – 440 VAC
Output voltage: 230 VAC

Duty cycle: continuous
Frequency: 50/60
Protection rating: IP 00
Terminal block protection rating: IP 20
Ambient temperature: 40°C MAX
Thermal insulation class: B/130°C or F/155°C
Protection against direct and indirect contact: class I
Winding material: copper
Standards: EN61558-2-4
Approvals: cURus (insulation systems UL CSA fi le number E340840)

Optional accessories

Terminal blocks with fuse-holder, protection thermal switches, electrostatic shield, horizontal installation

Code Pri 400Code Pri 415Code Pri 440Power (VA)Length L (mm)Depth P (mm)Height H (mm)Fixing XFixing YWeight (Kg)
TTM50BATTM50BBTTM50BC5001801101801508011
TTM10CATTM10CBTTM10CC10002401102302008517
TTM15CATTM15CBTTM15CC15002401202302009520
TTM20CATTM20CBTTM20CC200024013023020010525
TTM25CATTM25CBTTM25CC250024014523020012030
TTM30CATTM30CBTTM30CC300030016029025011240
TTM35CATTM35CBTTM35CC350030016029025011240
TTM40CATTM40CBTTM40CC400030017029025012245
TTM50CATTM50CBTTM50CC500030018029025013253
TTM60CATTM60CBTTM60CC600030019029025014254
TTM70CATTM70CBTTM70CC7000360170-21035032513475
TTM80CATTM80CBTTM80CC8000360180-22035032514478
TTM10DATTM10DBTTM10DC10000360190-23035032515483
TTM12DATTM12DBTTM12DC12000420250420375160100
TTM15DATTM15DBTTM15DC15000420260420375170110
TTM18DATTM18DBTTM18DC18000480300480423175155
TTM20DATTM20DBTTM20DC20000480320480423195170
TTM25DATTM25DBTTM25DC25000480330480423205190