USE

Single-phase transformers with direct safety output
USE
USE
USE
USE

Approved transformers for safety circuits. The insulation between the primary and secondary winding is double and created with the UL CSA certified insulation system. USE series units are designed for general use.

USE

Technical data

Power: 30 ÷ 2000 VA
Input voltage: 0 230 400 VAC
Secondary circuit output voltage: 0 12 or 0 24 VAC

Duty cycle: continuous
Frequency: 50/60 Hz
Protection rating: IP 00
Terminal block protection rating: IP 20
Ambient temperature: +40°C MAX
Thermal insulation class: B/130°C ENEC – F/155°C UL
Protection against direct and indirect contact: class I
Winding material: copper
Standards: EN61558-2-6
Approvals: cURus (insulation systems AB155 UL CSA file number E340840)
ENEC05 – KEMA-KEUR

Pri. 230 400
Sec. 12
Cod
Pri. 230 400
Sec. 24
cod
Power (VA)Length L (mm)Depth P (mm)Height H (mm)Fixing
X
Fixing
Y
Weight (Kg)Losses
FE W
Losses
CU
Vcc
%
USE30AAUSE30AB3076708553491,371010,5
USE50AAUSE50AB5076758553531,588,69,5
USE63AAUSE63AB6385859060601,911,88,69
USE80AAUSE80AB80859090606521388,3
USE10BAUSE10BB10085959060702,2147,88,5
USE15BAUSE15BB15097909868722,81766,5
USE20BAUSE20BB200971009868874235,85
*USE25BAUSE25BB2501209513080774,52565,5
*USE30BAUSE30BB30012010013080835,5306,35,2
*USE40BA*USE40BB40012011013080936354,85
*USE50BA*USE50BB500120120130801037,5374,75
*USE55BA*USE55BB55013511714090888405,54,4
*USE60BA*USE60BB600150110155105808,54554
*USE63BA*USE63BB630150110155105808,54554
*USE70BA*USE70BB70015012015510590104843,8
*USE80BA*USE80BB80015013015510510011,5503,83,5
*USE10CA*USE10CB1000150140155105110135833,2
*USE13CA*USE13CB130018014518012811016853,13,8
*USE16CA*USE16CB160018014518012811018883,24
*USE20CB200019316019013512523922,53