DIN

Single-phase IP20 transformers safety - isolation
DIN
DIN
DIN

Transformers for safety and isolation circuits. The insulation between the primary and secondary winding is double and created with the UL CSA certifi ed insulation system. DIN series units for general use with omega rail or screw fi xing are manufactured on demand.

DIN

Technical data

Power: 30 ÷ 300 VA

Input voltage: 100 ÷ 480 VAC

Secondary circuit output voltage: 12 ÷ 480 VAC

Duty cycle: continuous
Frequency: 50/60 Hz
Protection rating: IP 20
Ambient temperature: +40°C MAX
Thermal insulation class: B/130°C or F/155°C
Protection against direct and indirect contact: class II
Winding material: copper
Standards: EN61558-2-4 EN61558-2-6
Approvals: cURus (insulation systems AB155 UL CSA fi le number E340840)

Pri. 230 400 Sec. 12Pri. 230 400 ±15V Sec. 24Power (VA)Length L (mm)Depth P (mm)Height H (mm)Fixing XFixing YWeight (Kg)Losses FE WLosses CUVcc %
DINS30AXXDINI30AXX30901068768,54,51,321,58,3
DINS50AXXDINI50AXX50901068768,54,51,62,11,88
DINS63AXXDINI63AXX63901069668,54,51,72,12,47
DINS80AXXDINI80AXX809010610668,54,51,92,22,56,5
DINS10BXXDINI10BXX1009010610668,54,522,32,56,5
DINS16BXXDINI16BXX160126106127961213,8536
DINS20BXXDINI20BXX2001261361279612145,79,54,7
DINS25BXXDINI25BXX250126136127961214,85,79,74,7
DINS30BXXDINI30BXX30012613612796121569,84,5